The control parameters can be loaded with
predetermined default values. These data are
the typical values loaded in the instrument prior
to shipment from factory. To load the default
values proceed as follows:
a) The SMART function should be disabled.
b) The safety lock must be OFF.
c) The upper display will show the processe
variable while the lower display will show
the set point value or the current measure
(1603E type).
d) In normal display mode, held down
pushbutton and press pushbutton; the
display will show:
e) Within 10 seconds press pushbutton.
The display will show:
ìf) Press FUNC pushbutton; the display will show:
This means that the loading procedure has been
initiated. After about 3 seconds the loading
L.dt.L.dt.
L.dt.L.dt.
L.dt.
dl.fdl.f
dl.fdl.f
dl.f
dl.ndl.n
dl.ndl.n
dl.n
procedure is terminated and the instrument
reverts to NORMAL DISPLAY mode.
The following is a list of the default operative
parameters loaded during the above procedure:
PARAM. DEFAULT VALUE
SPSP
SPSP
SP = minimum range-value
SP2SP2
SP2SP2
SP2 = minimum range-value
tt
tt
t = 8.0 mm.s
n.rSn.rS
n.rSn.rS
n.rS = OFF
AL.1AL.1
AL.1AL.1
AL.1 = minimum range-value for process alarms;
0 for deviation or band alarms
HS.1HS.1
HS.1HS.1
HS.1 = 0.1 %
AL.2AL.2
AL.2AL.2
AL.2 = minimum range-value for process alarms;
0 for deviation or band alarms
HS.2HS.2
HS.2HS.2
HS.2 = 0.1 %
PbPb
PbPb
Pb = 4.0 %
HSHS
HSHS
HS = 0.5 %
titi
titi
ti = 1603E: 04.0 1601E: 04.00 (4 minutes)
tdtd
tdtd
td = 1603E: 1.00 1601E: 01.00 (1 minute)
IPIP
IPIP
IP = 30 % for one control output
0 % for two control outputs
CC
CC
C = 20 seconds
C2C2
C2C2
C2 = 10 seconds for P6 = AIr
4 seconds for P6 = OIL
2 seconds for P6 = H2O
rCrC
rCrC
rC = 1.00 for P6 = AIr
0.80 for P6 = OIL
0.40 for P6 = H2O
OLPOLP
OLPOLP
OLP =0
rLrL
rLrL
rL = initial scale value (P2)
rHrH
rHrH
rH = full scale value (P3)
OLHOLH
OLHOLH
OLH = 100 %
tOLtOL
tOLtOL
tOL = infinite