3
GBGB
GBGB
GB
RTD INPUTRTD INPUT
RTD INPUTRTD INPUT
RTD INPUT
Fig. 4 RTD CONNECTION
SAFETY NOTESSAFETY NOTES
SAFETY NOTESSAFETY NOTES
SAFETY NOTES:
1) Do not run input wires together with power line
cables.
2) Pay attention to the line resistance; a resistance
higher than 20 /wire may cause measurement
errors.
3) When shielded cable is used, it should be
grounded at one side only to avoid ground loop
currents.
4) The impedence of the 3 wires must be the
same.
8
RTD
10
9 8
RTD
10
9
11
12
Log. input 2
LOGIC INPUTLOGIC INPUT
LOGIC INPUTLOGIC INPUT
LOGIC INPUT
SAFETY NOTE:SAFETY NOTE:
SAFETY NOTE:SAFETY NOTE:
SAFETY NOTE:
1) Do not run logic input wiring together with
power cables.
2) Use an external dry contact capable of
switching 8 mA, 8 V DC.
3) The instrument needs 300 ms to recognize a
contact status variation.
4) The logic input is
NOT NOT
NOT NOT
NOT isolated by the
measuring input
Fig. 5 - LOGIC INPUT WIRING
The logic input can be programmed as:
A) Set point selector
A.1) In this case it will operate as follows:
logic input operat. set point
open SP
close SP2
B) Start timer
In this case it will operate as described at
paragraph 5.10 (Timer modes description).