OUT 1 (Heating):OUT 1 (Heating):
OUT 1 (Heating):OUT 1 (Heating):
OUT 1 (Heating):
Relay out with SPDT contact;
a) Out contact 3A / 250 V AC on resistive load.
b) Logic voltage for solid state relay command.
Logic state 1:24 Vdc +20% @ 1mA,
14V +20% @20 mA
Logic state 0: <0.5V
OUT 2 (Cooling or alarm 1)OUT 2 (Cooling or alarm 1)
OUT 2 (Cooling or alarm 1)OUT 2 (Cooling or alarm 1)
OUT 2 (Cooling or alarm 1)
Relay out with SPST contact;
Out contact 2A/250V AC on resistive load.
OUT 3 (alarm 2)OUT 3 (alarm 2)
OUT 3 (alarm 2)OUT 3 (alarm 2)
OUT 3 (alarm 2)
Relay out with SPST contact;
Out contact 2A/250V AC on resistive load.
NOTENOTE
NOTENOTE
NOTE: the "OUT 3" and the "logic input" options
are mutually exclusive.
7.57.5
7.57.5
7.5
CPI – CONFIGURATION PORTCPI – CONFIGURATION PORT
CPI – CONFIGURATION PORTCPI – CONFIGURATION PORT
CPI – CONFIGURATION PORT
INTERFACEINTERFACE
INTERFACEINTERFACE
INTERFACE
The instrument has a lateral socket into which a
special five-pin connector can be inserted. This
connector, supplied as an option together with its
interface, can connect to the RS232 port of a
normal PC on which the management software
must be installed.
By means of the software the configuration can be
managed directly from the PC. In this case the
instrument display and keypad are not operative.
8.8.
8.8.
8.
MAINTENANCEMAINTENANCE
MAINTENANCEMAINTENANCE
MAINTENANCE
WARNING WARNING
WARNING WARNING
WARNING
Electric shock HazardElectric shock Hazard
Electric shock HazardElectric shock Hazard
Electric shock Hazard
Disconnect all power before servicing controller.
Failure to do so could result in personal injury or
property damage.
1) SWITCH THE EQUIPMENT OFF (power supply,
relay out, etc.).
2) Take the instrument out of it case.
3) Using a vacuum cleaner or a compressed air jet
(max. 3 kg/cm
2
) remove all deposits of dust and
dirt which may be present on the louvers and on
the internal circuits being careful not to damage
the electronic components.
4) To clean external plastic or rubber parts use
only a cloth moistened with:
- Ethyl Alcohol (pure or denatured) [C
2
H
5
OH] or
- Isopropyl Alcohol (pure or denatured)
[(CH
3
)
2
CHOH] or
- Water (H
2
O).
5) Make sure that there are no loose terminals.
6) Before putting the instrument back in its case,
make sure that it is perfectly dry.
7) Put the instrument back and turn it ON.
CPI connection socket
1601-03-1-CX.pmd 13/01/2004, 10.4328