Timer mode 2 [P22 = 6]Timer mode 2 [P22 = 6]
Timer mode 2 [P22 = 6]Timer mode 2 [P22 = 6]
Timer mode 2 [P22 = 6]
When the contact is closed, the instrument
controls using SP as operative set point.
When the contact has been opened, the
instrument selects SP2 as operative set point and
starts the time count down.
When the time count is equal to 0 the instrument
comes back to the SP set point and the output 2
will be energized.
The Out 2 reset will be made when the logic input
will be closed again.
1603E display management1603E display management
1603E display management1603E display management
1603E display management: when the
instrument starts the time count down, the upper
display shows the measured value while the lower
display shows time count down.
1601E display management1601E display management
1601E display management1601E display management
1601E display management: when the
instrument starts the time count down, the display
shows the time count down.
Pushing pushbutton it is possible to display the
measured value.
NOTENOTE
NOTENOTE
NOTE: for both instruments, when the time is
finished the instrument comes back to the normal
display mode.
SP2
SP
Programmed
time
Time
Output 2
OFF
OFF ON OFF
Contact
Closed Open Open
Closed
Stop Run Stop Run Stop Run
Timer mode 3 [P22 = 7]Timer mode 3 [P22 = 7]
Timer mode 3 [P22 = 7]Timer mode 3 [P22 = 7]
Timer mode 3 [P22 = 7]
When the contact is closed, the instrument
controls using SP as operative set point.
When the contact has been opened the instrument
operates as follows:
- it selects SP2 as operative set point
- it starts the time count down
- it energizes the Output 2
When the time count is equal to 0 the instrument
comes back to the SP set point and the output 2
will be reset.
1603E display management1603E display management
1603E display management1603E display management
1603E display management: when the
instrument starts the time count down, the upper
display shows the measured value while the lower
display shows time count down.
1601E display management1601E display management
1601E display management1601E display management
1601E display management: when the
instrument starts the time count down, the display
shows the time count down.
Pushing pushbutton it is possible to display the
measured value.
NOTENOTE
NOTENOTE
NOTE: for both instruments, when the time is
finished the instrument comes back to the normal
display mode.
SP2
SP
Time
Output 2
OFF
ON OFF
Contact
Closed Open Open