3) Press the FUNC pushbutton to save the new
value and go to the next parameter.
4) Press SMT to return to the previous parameter
without saving.
NOTESNOTES
NOTESNOTES
NOTES:
1) If, during parameter modification, no
pushbutton is pressed for more than 10
seconds, the instrument automatically reverts
to the “normal display mode” and the new
setting of the last parameter will be lost.
2) In the “normal display”, on pressing pushbutton
or and keeping it pressed for more than
two seconds, one can directly access the set
point value, which can be modified by pressing
or again (see section 5.7).
3) The instrument does not display all the possible
parameters, but only those which are in
agreement with:
a) The instrument configuration (see section 4).
b) The setting of parameter P14 (see section
4).
c) The setting of the proportional band (see
section 5.5).
5.25.2
5.25.2
5.2
INDICATORSINDICATORS
INDICATORSINDICATORS
INDICATORS
SMT Flashes when the first part of the SMART
algorithm is active.
Lit when the second part of the SMART
algorithm is active.
OUT1 Lit up when out 1 is ON.
OUT2 A) When used as event or cooling output it
lit up when out 2 is ON.
B) When used as alarm indication:
B.1) Lit if only Alarm1 is in alarm
condition.
B.2) Flashing at slow rate (0.5 Hz) if only
Alarm 2 is in alarm condition.
B.3) Flashing at fast rate ( 2 Hz) if both
alarms are in alarm condition.
°C Lit up if the temperature is displayed in °C.
°F Lit up if the temperature is displayed in °F.
SP (1601E only) Lit when the display shows the
operative set point.
In additionIn addition
In additionIn addition
In addition:
a) The decimal point on the right hand of the
LSD of the upper display, for 1603E, or of
the display, for 1601E, flashes when the
instrument is working with SP2.
b) The decimal point on the left hand of the
LSD of the lower display, for 1603E, or of
the display, for 1601E, flashes when the
display shows the time count down.
5.35.3
5.35.3
5.3
FUNCTION OF THE PUSHBUTTONSFUNCTION OF THE PUSHBUTTONS
FUNCTION OF THE PUSHBUTTONSFUNCTION OF THE PUSHBUTTONS
FUNCTION OF THE PUSHBUTTONS
FUNC Saves the new value of the selected
parameter and goes to the next
parameter (increasing order).
SMT Enables or disables the SMART
function and scrolls back all the
parameters without saving them.
Increases the value of the selected
parameter or (1601E only) displays the
set point value or the measured value.
Decreases the value of the selected
parameter.
+ FUNC Enables/disables the "LAMP TEST".
NOTENOTE
NOTENOTE
NOTE: The operator parameters must be modified
within 10 seconds. If, during operator parameter
modification, no pushbutton is pressed during this
time, the instrument automatically reverts to the
“normal display mode”. Saving only the parameter
modifications which were followed by pressing the
FUNC pushbutton.
1601-03-1-CX.pmd 13/01/2004, 10.4315