rC Relative Cooling gain.
This parameter is available only when
device is configured with two control
outputs and Pb is different from zero.
Range: from 0.20 to 1.00
Note: When the device is working with
SMART algorithm and P28 is set to On
the RCG value is limited in accordance
with the selected type of cooling media:
- from 0.85 to 1.00 when P8 = AIr
- from 0.80 to 0.90 when P8 = OIL
- from 0.30 to 0.60 when P8 = H2O
OLAP Dead band/Overlap between H/C
outputs.
This parameter is available only when
device is configured with two control
outputs and Pb is different from zero.
Range: from -20 to 50 % of the
proportional band.
A negative OLAP value shows a dead
band while a positive value shows an
overlap.
rL Set point low limit
Range: from initial scale value (P3) to rH.
Note: When P3 has been modified, rL
will be realigned to it
rH Set point high limit
Range:from rL to full scale value (P4)
Note: When P4 has been modified, rH
will be realigned to it
Grd1 Ramp applied to an increasing set
point change
Range: from 1 to 100 digits per minute.
Above this value the display shows Inf
meaning that the transfer will be done as
a step change.
Grd2 Ramp applied to a decreasing set
point changes
For other details see Grd1 parameter.
Note:When device is working with SMART
algorithm the Pb value will be limited by
P29, P30 and P31 parameters.
HyS Hysteresis for ON/OFF control action
This parameter is available only when
Pb=0.
Range: from 0.1% to 10.0% of the input
span.
ti Integral time
This parameter is skipped if Pb=0 (ON/
OFF action).
Range: from 00.01 to 20.00 [mm.ss].
Above this value the display blanks and
integral action is excluded
Note: When the device is working with
SMART algorithm, the minimum value of
the integral time will be limited by P32
parameter.
td Derivative time
This parameter is skipped if Pb=0
(ON/OFF action) or P40 = Pi.
Range:From 00.00 to 10.00 mm.ss.
Notes: When device is working with
SMART algorithm the td value will be
equal to a quarter of Ti value.
IP Integral pre-load.
This parameter is skipped if Pb=0
(ON/OFF action).
For one control output, it is programma-
ble from 0 to 100 % of the output span.
For two control outputs it is programma-
ble from -100% (100 % cooling)
to 100 % (100 % heating).
Cy1 Output 1 cycle time
Range:From 1 to 200 s.
Cy2 Output 2 cycle time
This parameter is available only if P 7 is
equal to 4.
Range:From 1 to 200 s.